Материал на бронята на термодвойката
Остави съобщение
Правилното използване на бронирани термодвойки може не само точно да получи температурни стойности и да гарантира качеството на продукта, но и да спести консумация на материали на термодвойки, спестявайки пари и осигуряване на качество на продукта . неправилна инсталация, грешки като термична проводимост и забавяне на времето са основните грешки при използването на термодвойки .}
1. Грешки, въведени чрез неправилна инсталация:
The installation position and insertion depth of the armored thermocouple cannot reflect the actual temperature of the furnace. In other words, the thermocouple should not be installed too close to the door or the heating place, and the insertion depth should be at least 8 to 10 times the diameter of the protection tube. The gap between the thermocouple protection tube and the wall is not filled with insulating material, which causes heat overflow or cold air intrusion in the furnace. Therefore, the gap between the thermocouple protection tube and the furnace wall hole should be blocked with insulating materials such as refractory mud or asbestos rope to prevent hot and cold air convection and affect the accuracy of temperature measurement. The cold end of the thermocouple is too close to the furnace body, causing the temperature to exceed 100℃. The installation of the thermocouple should avoid strong magnetic fields and strong electric fields as much as possible, so the thermocouple and the power cable should not be installed in the same conduit to avoid interference and errors. Thermocouples cannot be installed in areas where the measured medium rarely flows. When using thermocouples to measure the temperature of the gas in Епруветката, термодвойката трябва да бъде инсталирана спрямо посоката на потока и напълно в контакт с газовете . 2. грешки, въведени чрез разграждане на изолация:
Ако термодвойката е изолирана, защитната тръба и платката за теглене на тел са твърде мръсни или имат твърде много солни остатъци, което води до лоша изолация между полюсите на термодвойката и стената на пещта, която е по -сериозна при високи температури ., това не само ще причини загубата на термоелектрически потенциал, но и въведе интерференция .
3. Грешки, въведени от термична инерция:
The thermal inertia of the armored thermocouple causes the indication value of the instrument to lag behind the change of the measured temperature. This effect is particularly prominent when performing rapid measurements. Therefore, thermocouples with thinner thermocouples and smaller protection tube diameters should be used as much as possible. When the temperature measurement environment permits, the protection tube can even be removed. Due to the measurement lag, the amplitude of the temperature fluctuation detected by the thermocouple is smaller than the amplitude of the furnace temperature fluctuation. The greater the measurement lag, the smaller the amplitude of the thermocouple fluctuation, and the greater the difference with the actual furnace temperature. When using a thermocouple with a large time constant to measure or control temperature, although the temperature displayed by the instrument fluctuates slightly, the actual furnace temperature may fluctuate greatly. In order to accurately measure the temperature, a thermocouple with a small time constant should be selected. The time constant is inversely proportional to the heat transfer coefficient and is proportional to the diameter of the hot end of the thermocouple, the density of the material and the specific Teat . Ако искате да намалите постоянната постоянна време, в допълнение към увеличаването на коефициента на топлопреминаване, най -ефективният начин е да се сведе до минимум размера на горещия край ., използвани, материали с добра термична проводимост, тънки стени и малък вътрешен диаметър защитни ръкави, обикновено се използват.}} in по -прецизни измервания на температурата. Термодвойките лесно се повредят и трябва да бъдат калибрирани и заменени във времето .
4. Грешка при термично съпротивление:
При високи температури, ако върху защитната тръба има слой от въглищна пепел и прах, залепнал за нея, термичното съпротивление се увеличава, което пречи на проводимостта на топлината. В този момент показанието на температурата е по-ниско от истинската стойност на измерената температура. Следователно, външната част на защитната тръба на термопарите трябва да се поддържа чиста, за да се намали грешката.